2×4.0mm²-Black/Red (H1Z2Z2-K) Twin Core Solar (PV) Cable (NO.7194103)- IEC62930/EN50618:2014

Product Description

2×4.0mm⊃2;-Black/Red (H1Z2Z2-K)
NO.7194103- IEC62930/EN50618:2014

General characteristics:

Appllcation:

Specifically designed to connect photovoltaic system components inside and outside buildings
and facilities under high mechanical demands and extreme weather conditions.

Cable Construction

Conductor


Metarial

Tinned annealed copper

Area(mm⊃2;) :

2×4.0

Construction(N/mm) :

56/0.285±0.005

Stranded diameter(mm) :

2.463 (Ref.)

Insulation

125℃ XLPE Black

Min. thickness (mm) :

0.7

Nom. thickness (mm) :

0.8 (Ref.)

Standard diameter (mm) :

4.05±0.1

Jacket

125℃ XLPE, Black/Red

Min. thickness (mm) :

0.7

Nom. thickness (mm) :

0.8 (Ref.)

Outer diameter (mm) :

5.70±0.10×(11.5±0.10

Making

ZION COMMUNICATION TÜV  SÜD   IEC62930  
EN50618:2014   H1Z2Z2-K   2×4.0mm⊃2;  -40℃  to +90℃   
DC  1500V     HALOGEN  FREE  LOW  SMOKE









Package


100M/Roll, 500M/Wooden Drum    


PALLET



















Electrical properties

Nominal Voltage:

H1Z2Z2-K:   DC 1.5KV   AC 1.0/1.0KV

Ambient Temperature:

-40℃~+90℃

Max.Temperature at conductor:

+125℃

Service life:

25 years ( -40~+90℃)

Voltage:

600/1000V

Temperature:

-40~90℃

Conductor resistance (20℃):

5.09Ω/km

Insulation resistance (70℃):

≥1000 MΩ/km

Withstand voltage(V/5min)

AC6500

Speak voltage(V/5min)

AC6500

Min bending radius(mm)

4*D


Main performance parameter of finished cable

Voltage test of finished cable

Min.time of dipping in water

≥1(h)

Testing voltage (AC)

6500(V)

Min.voltage applying time at one time

5(min)

Test result

no breakdown

Sheated surface resistance

Length of specimen:

250mm

Test result

≥109Ω

Penetrate the insulation resistance

Temperature

20℃

Test result

≥1014Ω

High temperature stress

Temperature

140℃

A: with 1.2 Voltage test

A: No breakdown

B: deep pressure

B: Wall thickness 50%

Damp-heat test

Temperature

90℃

Humidity

85%

Aging before and after the tenslle strength of Change

≤30%

Aging before and after the elongation at break of Change

≤-30%


Acid-alkali Resistance

Min.time of dipping in

168h

Aging before and after the tensile strength of Change

≤-30%

Elongation

≥100

Low-temperature bending

Temperature

-40℃

Time

16h

Test result

No crack

Ozone resistance

Ozeone concentration %

200±50x10-6

Time

72h

Test result

No crack

Heat schrinkable jacket test

Test result

≤2%

Flame retardant-Vertical burn


Flxture on the lower edge from the starting point and carbonization

≥50mm

Burning fuel downward from the lower edge of bottom fixture

≤540mm

Halogen content of non-metallic materials

Test result


Chlorine and bromine content

HCL≤0.5HBr≤0.5%

Fluoride content

F≤0.1%

The inner layer of insulation and sheath of the mechanical properties

Test result


Aging before tensile strength

8.0N/mm⊃2;

Aging before elongation

1.25

Aging before and after the tensile strength of change

-0.3

Aging before and after the elongation at break of change

-0.3

Hot extension

Temperature

200℃

Test result-The inner layer of insulation and sheath


Elongation under load