NO.7110412 PH30 4×2.5mm² Fire Alarm Cables

Specification

PH30 4×2.5mm⊃2;

Fire Alarm Cables

NO.7110412

CABLE CONSTRUCTION:

Conductor:

2.5mm(sqmm) Plain annealed copper wire,
class 1,2 or 5 according to EN60228.

Insulation:

Fire resistant silicone rubber
BS 6387 CWZ,EN 50200 PH30,IEC 60331

Dia.over Dielectric:4x(0.0126"(3.2 mm))

Insulation Color:

Blue/Brown

Separator:

PET Foil

Drain Wire:

0.80 mm Solid tinned copper

Shield:

Aluminum PET (100% Coverage 20% overlapping)

Jacket:

FR-LSZH (Red or White)

Dia.over Jacket: 0.383''±0.006''(9.75±0.15mm)

HFFR EN 502902,BS7655 LTS1/LTS3

Print Legend:

HELLOSIGNAL Fire Alarm Cable PH30 2.5mm⊃2; 4 Cores Class N                                  

BC BS 50200:2006 NO.7110412 ××××M/FT  


ELECTRICAL PROPERTIES(at20℃):

Min.Bend Radius:

8×Diameter

Min.Insulation resistance:

200 MΩ/km

Max.Working Temperature:

.-30~+90

Test voitage:

2000 V

Max.Operating voitage:

300 V / 600 V

Max.resistance of Cond:

Class1,27.4Ω/km

Class58.0Ω/km

Current Carrying Capacity:



Nominal Capacitance:




Cross Section :

Test Standards

Flame Tests

Insualtion Integrity

Smoke Density

Corrosive Gas Easurement

BS 4066 part 1 & 3

IEC 60331

BS 7622

BS EN 50267-2-2

EN 50266-2-4

BS 6387 CWZ

IEC/EN 61034

IEC 60754-2

IEC 60332-3-24

EN 50200 PH30

HD 606


IEC/EN 60332-1





Order Informations :

Package

100M/Wooden Spool,200M/Wooden Spool,500M/Wooden Spool

Delivery time

Normally 25 days after received the deposit.

Brand

HELLOSIGNAL® OR OEM

                                                                                                                                                                                                       

 


NO.7110411 PH30 4×1.5mm² Fire Alarm Cables

NO.7110410 PH30 4×1.0mm² Fire Alarm Cables

NO.7110403 PH30 2×2.5mm² Fire Alarm Cables

NO.7110402 PH30 2×1.5mm² Fire Alarm Cables