Cable & Wire | Good quality and good service based on reasonable prices.
info@zion-communication.com

loading

16mm²-B (PV1-F / H1Z2Z2-K) Single core Solar Cable

  • Solar cable

  • hellosignal

  • NO.7194005

  • Power Cables

  • Normally 25 working days

  • NINGBO, SHANGHAI

Availability:

16mm²-B (PV1-F / H1Z2Z2-K)

(NO.7194005)


 General characteristics:

General characteristics


 Application:

Specifically designed to connect photovoltaic system components inside and outside buildings

and facilities under high mechanical demands and extreme weather conditions.



 Cable Construction:


Solar Cable


Conductor:

Material: Tinned annealed copper

Area(mm²): 1*16

Construction(N/mm): 128/0.40

Conductor(Dia./mm): 5.25


Insulation: 120℃ XLPE

Standard thickness (mm): 0.9

Standard diameter (mm): 7.05±0.1


Jacket: 120℃ XLPE, Black

Standard thickness (mm): 1.2

Outer diameter (mm): 9.45±0.2

Making: ZION COMMUNICATION PV1-F / H1Z2Z2-K 1x16mm² UV Res

DC 1.0KV AC 0.6/1.0KV (DC 1.5KV AC 1.0/1.0KV)

SOLAR CABLE



 Package:

BOX  (art.code ZC-100-16mm/ZC-500-16mm) 


package


PALLET Size:

Amount of boxes on one pallet:

Weight of total pallet:

Cable length pallet:



 Electrical properties:

Nominal Voltage:

PV1-F: DC 1.0KV / AC 0.6/1.0KV

H1Z2Z2-K: DC 1.5KV / AC 1.0/1.0KV


Temperature Ratings:

Ambient Temperature: -40℃ to +90℃

Max. Temperature at Conductor: +120℃

Service Life: >25 years (within -40℃ to +90℃)


Resistance & Withstand Voltage:

Conductor Resistance (20℃): 1.24Ω/km

Insulation Resistance (70℃): ≥1000 MΩ/km

Withstand Voltage (5 min): AC 6500V


Bending Radius:

Min. Bending Radius: 5 × Diameter (D)



 The main performance parameter of finished cable:

  • Performance of Finished Cable

Voltage Test:

Min. Dipping Time in Water: ≥1 hour

Testing Voltage (AC): 6500V

Min. Voltage Applying Time: 5 min

Test Result: No breakdown

Sheath Surface Resistance:

Length of Specimen: 250mm

Test Result: ≥10⁹Ω

Insulation Resistance at 20℃:

Test Result: ≥10¹⁴Ω

High Temperature Stress (140℃):

Voltage Test (1.2V): No breakdown

Deep Pressure: Wall thickness reduced by 50%

Damp-Heat Resistance (90℃, 85% Humidity):

Tensile Strength Change: ≤30%

Elongation at Break Change: ≤-30%


  • Chemical & Mechanical Resistance

Acid-Alkali Resistance:

Dipping Time: 168 hours

Tensile Strength Change: ≤-30%

Elongation: ≥100%

Low-Temperature Bending (-40℃, 16h):

Test Result: No crack

Ozone Resistance:

Ozone Concentration: (200±50)×10⁻⁶

Test Time: 72 hours

Test Result: No crack

Heat Shrinkable Jacket Test:

Test Result: ≤2% Shrinkage


  • Flame Retardancy & Halogen Content

Flame Retardant – Vertical Burn Test:

Carbonization Length: ≥50mm

Downward Flame Spread: ≤540mm

Halogen Content (Non-Metallic Materials):

Chlorine & Bromine (HCl / HBr): ≤0.5%

Fluoride (F): ≤0.1%


  • Mechanical Properties of Insulation & Sheath

Before Aging:

Tensile Strength: 8.0 N/mm²

Elongation: 125%

After Aging:

Tensile Strength Change: ≤-30%

Elongation at Break Change: ≤-30%

Hot Extension (200℃):

Elongation Under Load: ≤100%

Elongation After Unloading: ≤25%



Previous: 
Next: 
We use cookies to enable all functionalities for the best performance during your visit and to improve our services by giving us some insight into how the website is being used. Continued use of our website without changing your browser settings confirms your acceptance of these cookies. For details, please see our privacy policy.
×