Fire Resistant Cable 2 × 2.5 sq mm | IEC 60331-21 (FE90) / LSZH / BS 6387 Compliant (Red RAL 3000)


FR331-OS Fire Resistant Cable structure


General Information

Item Specification
Product Name Fire Resistant Cable
Model No. FR331-0S-0225
Construction Type CU / FR / OS / LSZH (Overall Screened)
Conductor Material Stranded Bare Copper (Class 5, EN 60228)
Conductor Size 45 × 0.25 mm
Nominal Cross Section 2 × 2.5 sq mm
Rated Voltage 300 / 500 V
Operating Temperature −30 °C ~ +90 °C
Outer Color Red RAL 3000
Applicable Standards IEC 60331-21 (FE90), BS 6387 CAT B/C, IEC 60332-1-2, IEC 60332-3-24, EN 50266-2-4, CE, RoHS


Construction Details

Component Material / Description Standard Dimensions
Conductor Stranded Bare Copper EN 60228 45 × 0.25 mm
DC Resistance (20 °C) EN 60228 7.98 Ω/km
Insulation Silicone Rubber (Heat Resistant) IEC/EN 60811-203 0.5 mm thick
Insulation Diameter IEC/EN 60811-201 3.1 ± 0.1 mm
Insulation Colors Brown / White
Insulation Resistance > 200 MΩ/km
Overall Screen Aluminum Foil (Overlapped) 0.04 × 24 mm
Drain Wire Tinned Copper (7 × 0.3 mm)
Outer Sheath LSZH (Low Smoke Zero Halogen) IEC/EN 60811-202 0.7 mm thick
Outer Diameter IEC/EN 60811-203 7.8 ± 0.2 mm
Pitch of Twist 136 ± 10 mm
Inductance 2.3 mH/km
High Voltage Test EN 50288-7 2.0 kV / 1 min


Fire & Safety Performance

Test Item Standard Description / Requirement
Fire Resistance IEC 60331-21 (FE90) / BS 6387 CAT B, CAT C Maintains circuit integrity for 90 min at 750–850 °C
Flame Propagation IEC 60332-1-2 / IEC 60332-3-24 / EN 50266-2-4 Restricts flame spread on single and bunched cables
Smoke Density IEC 61034-1/2 Low smoke emission ensures visibility during fire
Corrosive Gas Emission IEC 60754-1/2 / EN 50267 Low acid gas release, halogen-free
RoHS Compliance EU Directive 2011/65/EU Confirmed (Pb, Cd, Hg, Cr⁶⁺, PBB, PBDE Free)


 Electrical & Mechanical Characteristics

  • Insulation Resistance: > 200 MΩ/km

  • Voltage Withstand: 2.0 kV (1 min)

  • Inductance: 2.3 mH/km

  • Operating Temperature: −30 °C ~ +90 °C

  • Minimum Bending Radius: 10 × OD

  • Fire Survival Duration: 90 min (FE90)

 Applications

  • Designed for fire protection and emergency circuits requiring consistent operation during fire

  • Fire-alarm and emergency lighting systems

  • Smoke extraction and sprinkler control

  • Tunnels, hospitals, airports, and industrial facilities


 Key Features

  • FE90 Fire Resistance: Maintains circuit integrity for 90 minutes at 850 °C

  • LSZH Outer Sheath: Low smoke and non-toxic gas emission

  • Silicone + Aluminum Shield: Excellent heat and EMI protection

  • ✅ Certified Safety: Complies with IEC, BS, EN, CE and RoHS standards



Previous: 
Next: 
We use cookies to enable all functionalities for the best performance during your visit and to improve our services by giving us some insight into how the website is being used. Continued use of our website without changing your browser settings confirms your acceptance of these cookies. For details, please see our privacy policy.
×