Fire Cable
BS 6387:2013 Cat.C-W-Z
100m,500m,500ft,1000ft
roll, wooden spool, carton, pallet
10KM
Normally 15 working days
NINGBO, SHANGHAI
T/T, L/C at sight, D/P at sight
Availability: | |
---|---|
L*** Certificated
Conductors: Plain annealed copper wire, Class 5, stranded flexible.
Insulation: Special mix silicone rubber.
First Screen: Polyester (PET) foil with over 120% coverage.
Drain Wire: Tinned copper with an outer diameter of 0.80 mm.
Second Screen: Aluminum polyester tape with over 120% coverage.
Outer Sheath: Thermoplastic low smoke, halogen-free material.
Sheath Color Options: Red, white, or orange.
Insulation Resistance at 20°C: Greater than 200 MΩ·km.
Test Voltage (Core-Core/Core-Screen): 2000 V / 2000 V.
Mutual Capacitance: Less than 150 nF/km.
Operating Voltage: 300/500 V.
Lengths of 100 meters, 300 meters, or 500 meters on wooden spools.
Flame Propagation: Complies with BS 7629-1:2015 (Standard 60), BS 6387:2013 (CWZ), EN 50200:2015 Annex E (30 minutes), and BS 5839-1:2013 (Clause 26.2d standard).
Acidity: Meets EN/IEC 60754-1:2014 standards.
Smoke Density: Conforms to EN/IEC 61034-2:2005+A1:2013.
Rated as EN 50575:2016-Cca s1A, d0, a1.
During Operation: -30°C up to +180°C.
During Installation: -5°C up to +50°C.
HANGZHOU ZION Fire Cables BS 7629-1:2015 (Standard 60) STR Flexible
300/500V ×C×SQMM+BATCH NO.+METER MARKING
L*** Certificated
Conductors: Plain annealed copper wire, Class 5, stranded flexible.
Insulation: Special mix silicone rubber.
First Screen: Polyester (PET) foil with over 120% coverage.
Drain Wire: Tinned copper with an outer diameter of 0.80 mm.
Second Screen: Aluminum polyester tape with over 120% coverage.
Outer Sheath: Thermoplastic low smoke, halogen-free material.
Sheath Color Options: Red, white, or orange.
Insulation Resistance at 20°C: Greater than 200 MΩ·km.
Test Voltage (Core-Core/Core-Screen): 2000 V / 2000 V.
Mutual Capacitance: Less than 150 nF/km.
Operating Voltage: 300/500 V.
Lengths of 100 meters, 300 meters, or 500 meters on wooden spools.
Flame Propagation: Complies with BS 7629-1:2015 (Standard 60), BS 6387:2013 (CWZ), EN 50200:2015 Annex E (30 minutes), and BS 5839-1:2013 (Clause 26.2d standard).
Acidity: Meets EN/IEC 60754-1:2014 standards.
Smoke Density: Conforms to EN/IEC 61034-2:2005+A1:2013.
Rated as EN 50575:2016-Cca s1A, d0, a1.
During Operation: -30°C up to +180°C.
During Installation: -5°C up to +50°C.
HANGZHOU ZION Fire Cables BS 7629-1:2015 (Standard 60) STR Flexible
300/500V ×C×SQMM+BATCH NO.+METER MARKING